Beschreibung
10-channel Thermocouple Input Module
The “Z” version is another milestone in the development of I-7018 and a testament to excellence by ICP DAS R&D team. I-7018Z is specifically designed for extremely accurate thermocouple measurement. It features automatic cold-junction compensation for each channel. Current input and voltage input are supported. Another feature is that ten of its input channels can individually be confi gured with different kinds of analog input. I-7018Z also has open thermocouple detection and many protection mechanisms.
● Current Input, Voltage Input and Thermocouple Input
● Overvoltage Protection is up to 240 Vrms
● Individual Channel Configuration
● Open Thermocouple Detection
● 4 kV ESD Protection
● 3000 VDC Intra-Module Isolation
● Dual Watchdog
● Wide Operating Temperature Range: -25 ~ +75°C
Spezifikation
- Models
- I-7018Z
- Analog Input
- Channels
- 10
- Wiring
- Differential
- Sensor Types
- Thermocouple
- J, K, T, E, R, S, B, N, C, L, M, LDIN43710
- Voltage
- ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
- Current
- ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (requires an optional external 125 Ω resistor)
- Resolution
- 16-bit
- Accuracy
- ±0.1% of FSR
- Sampling Rate
- 10 Hz (Total)
- Input Impedance
- > 400 kΩ
- Common Voltage Protection
- ±200 VDC
- Individual Channel Configuration
- Yes
- Overvoltage Protection
- 240 Vrms
- Open Wire Detection
- Yes
- (for thermocouple only)
- Temperature Output Consistency
- Yes
- Stable Temperature Output in the Field
- Yes
- Models
- I-7018Z
- Communication
- Interface
- RS-485
- Bias Resistor
- No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
- Format
- (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
- Baud Rate
- 1200 to 115200 bps
- Protocol
- DCON
- Dual Watchdog
- Yes, Module (1.6 Seconds), Communication (Programmable)
- LED Indicator/Display
- System LED Indicator
- Yes, 1 as Power/Communication Indicator
- I/O LED Indicator
- -
- 7-Segment LED Display
- -
- Isolation
- Intra-Module Isolation, Field-to-Logic
- 3000 VDC
- EMS Protection
- ESD (IEC 61000-4-2)
- ±4 kV Contact for each Terminal
- EFT (IEC 61000-4-4)
- ±4 kV to Power
- Surge (IEC 61000-4-5)
- ±0.5 kV for Power Line
- Power
- Reverse Polarity Protection
- Yes
- Input Range
- +10 ~ +30 VDC
- Consumption
- 1.0 W
- Mechanical
- Dimensions (L x W x H)
- M-7018Z
- 116 mm x 73 mm x 35 mm
- DB-1820
- 78 mm x 65 mm x 22 mm
- DN-1822
- 103 mm x 96 mm x 27 mm
- Installation
- DIN-Rail or Wall Mounting
- Environment
- Operating Temperature
- -25 to +75°C
- Storage Temperature
- -40 to +85°C
- Humidity
- 10 to 95% RH, Non-condensing
Filterkriterien
- Host-Schnittstelle
- Seriell
- Eingabe Protokoll
- DCON
- Analog In
- 10
- Hersteller
- ICPDAS
- Status
- Standard
- Zollnummer
- 85176200
- WEEE Nummer
- DE76344510