Beschreibung
BACnetIP / ModbusRTU Gateway / 1xRS232 / 485
GW-5492 is a fully configurable universal Modbus RTU to BACnet/IP gateway. The GW-5492 includes BACnet/IP Server and Modbus RTU Master which is used to make Modbus RTU devices accessible on a BACnet network. BACnet (Building Automation and Control Networking) protocol has been designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, air-conditioning control…etc.
The GW-5492 contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus RTU registers to any combination of BACnet objects. Multiple BIBBs (DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM, DS-COV-B…etc.) are supported. All the data transfer is configurable using a standard Web browser.
● Quickly and Cost Effectively integrate networks
● Provide PWR/Communication Status indication LED
● Read/Write any standard Modbus register via BACnet
● No Programming Required
● Modbus register mapping configured via web interface
Spezifikation
- COM Interface
- GW-5492 CR
- COM Ports
- 2
- Protocol
- Modbus RTU
- Hierarchy
- Slave
- COM1
- RS-232 (RxD, TxD, and GND); Non-isolation
- COM2
- RS-485 (D2+, D2-); 2500 VDC; isolated
- Ethernet Interface
- GW-5492 CR
- Ethernet Ports
- 1
- Protocol
- BACnet/IP
- Transmission Speed
- 10/100 MB/s
- Hierarchy
- Server
- Installation
- GW-5492 CR
- Power Consumption
- 4.8 W
- Dimensions (WxLxH)
- 91 x 132 x 52 mm (WxHxD)
- Voltage Supply
- 10-30 VDC
- Operating Temperature
- -25 to 75°C
- Mounting
- Din Rail or Wall Mounting
- Housing
- Plastic
- Color
- Black
Filterkriterien
- Eingabe Protokoll
- ModbusRTU
- RS-232
- 01
- RS-485
- 01
- Hersteller
- ICPDAS
- Status
- Archiviert
- Zollnummer
- 85176200
- WEEE Nummer
- DE76344510