Description
8-channel Thermistor Input and 6-channel DO Module
I-7005 is used for measuring temperature by the thermistor. It supports many kinds of thermistors and features individual channel configuration which means that eight of its input channels can individually be confi gured with different kind of thermistor. Besides, it also supports user-defined types by specifying the Steinhart coeffi cients to add other thermistors and provide 6-channel digital outputs for alarm output. Adding 3000 VDC intramodule isolation and 120 VDC overvoltage protection for thermistor on I-7005 makes itself running with higher reliability. M-7005 supports Modbus RTU and DCON protocols which can be confi gured via software and all hardware specifi cations are the same as I-7005.
● 8-channel Thermistor Inputs
● Open Wire Detection
● User-Defined Types
● Individual Channel Configuration
● 120 VDC Overvoltage Protection for Thermistor
● 6-channel Digital Outputs for Alarm Output
● 4 kV ESD and EFT Protection
● 3000 VDC Intra-Module Isolation
● Dual Watchdog
● Wide Operating Temperature Range: -25 ~ +75°C
Specification
- Models
- I-7005
- Thermistor Input
- Channels
- 8
- Wiring
- 2-wire
- Sensor Types
- Precon ST-A3, Fenwell U, YSI L100, YSI L300, YSI L1000, YSI B2252, YSI B3000, YSI B5000, YSI B6000, YSI B10000, YSI H10000, YSI H30000, User-defined
- Resolution
- 16-bit
- Accuracy
- ±0.1% of FSR
- Sampling Rate
- 8 Hz (Total)
- Individual Channel Configuration
- Yes
- Overvoltage Protection
- 120 VDC
- Open Wire Detection
- Yes
- Resistance Measurement
- 200 kΩ Max.
- Digital Output
- Channels
- 6
- Type
- Open Collector
- Sink/Source (NPN/PNP)
- Sink
- Load Voltage
- +3.5 ~ +50 VDC
- Max. Load Current
- 650 mA/Channel
- Overvoltage Protection
- 60 VDC
- Overload Protection
- 1.4 A (with short-circuit protection)
- Power-on Value
- Yes
- Safe Value
- Yes
- Models
- I-7005
- Communication
- Interface
- RS-485
- Bias Resistor
- No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
- Format
- (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
- Baud Rate
- 1200 to 115200 bps
- Protocol
- DCON
- Dual Watchdog
- Yes, Module (1.6 Seconds), Communication (Programmable)
- LED Indicator/Display
- System LED Indicator
- Yes, 1 as Power/Communication Indicator
- I/O LED Indicator
- -
- 7-Segment LED Display
- -
- Isolation
- Intra-Module Isolation, Field-to-Logic
- 3000 VDC
- EMS Protection
- ESD (IEC 61000-4-2)
- ±4 kV Contact for each Terminal
- EFT (IEC 61000-4-4)
- ±4 kV for Power Line
- Surge (IEC 61000-4-5)
- ± 0.5 kV for Power Line
- Power
- Reverse Polarity Protection
- Yes
- Input Range
- +10 ~ +30 VDC
- Consumption
- 1.3 W
- Mechanical
- Dimensions (L x W x H)
- 123 mm x 72 mm x 35 mm
- Installation
- DIN-Rail or Wall Mounting
- Environment
- Operating Temperature
- -25 to +75°C
- Storage Temperature
- -40 to +85°C
- Humidity
- 10 to 95% RH, Non-condensing
Filter criteria